IMO/VIN
Callsign
Flag
Service
Year
9317858
V7RQ7
MARSHALL ISLANDS
Tank Ship
2005
Activity#
Port
Date
Activity - Description
Deficiencies
6905657
San Francisco, California
Feb 09, 20
Vessel Operational Control - Agency Action Complete
6686316
New Orleans, Louisiana
May 24, 19
Vessel Inspection - Approved Inspection
6314022
WASHINGTON, District of Columbia
Nov 22, 17
Incident Investigation - Agency Action Complete
6299592
Houston, Texas
Nov 08, 17
Vessel Inspection - Approved Inspection
1
0
System Subsystem Cause Deck/Cargo Inert Gas System
Description Due Date Resolved 1199- THE INERT GAS SYSTEM SHALL BE CAPABLE OF INERTING, PURGING AND GAS-FREEING EMPTY TANKS AND MAINTAINING THE ATMOSPHERE IN CARGO TANKS WITH THE REQUIRED OXYGEN CONTENT. THE IGG COMBUSTION AIR BLOWER IS INOPERABLE, INHIBITING THE INERTING CAPABILITIES OF THE INERT GAS SYSTEM. 74 SOLAS (14 CONS) II-2/4.5.5.3.1, 40AC. Yes
Resolved Date Resolution Nov 10, 17 SEC HOU-GAL PSC received a class report from ABS satisfying the requirement.
6241335
ATLANTIC BEACH, North Carolina
Aug 15, 17
Vessel Inspection - Approved Inspection
6093735
San Francisco, California
Feb 24, 17
Vessel Operational Control - Agency Action Complete
6017829
Houston, Texas
Oct 10, 16
Vessel Inspection - Approved Inspection
5132655
North Charleston, South Carolina
May 23, 15
Vessel Inspection - Agency Action Complete
5130526
Wilmington, North Carolina
May 20, 15
Vessel Inspection - Approved Inspection
1
0
System Subsystem Cause Deck/Cargo Inert Gas System
Description Due Date Resolved The inert gas system shall be capable of inerting, purging, and gas-freeing empty tanks and maintaining the atmosphere in cargo tanks with the required oxygen content. The inert gas generator oxygen sensor is malfunctioning. Jun 04, 15 Yes
Resolved Date Resolution May 23, 15 Sector Charleston received an email from class attesting to the proper installment and functionality of the O2 sensor.
5099292
Mobile, Alabama
Apr 08, 15
Vessel Inspection - Approved Inspection
5089379
Mobile, Alabama
Mar 29, 15
Vessel Inspection - Approved Inspection
1
0
System Subsystem Cause Electrical Lighting (emergency)
Description Due Date Resolved 0945-Emergency Lighting- Survival craft, its launching appliance, and the area of water into which it is to be launched shall be adequately illuminated by lighting supplied from the emergency source of electrical power. PSCO noted that the port and starboard emergency lighting was inoperable. 74 SOLAS 09 III/16.7 Yes
Resolved Date Resolution Apr 08, 15 Port and starboard embarkation emergency lighting fixtures were renewed and proven operational.
4796524
Warrenton, Oregon
Feb 15, 14
Vessel Inspection - Approved Inspection
4739346
WASHINGTON, District of Columbia
Oct 22, 13
Incident Investigation - Agency Action Complete
4618602
New Orleans, Louisiana
Jun 12, 13
Vessel Inspection - Approved Inspection
4542980
San Francisco, California
Mar 08, 13
Vessel Inspection - Approved Inspection
1
0
System Subsystem Cause Lifesaving Lifeboat Design Flaw
Description Due Date Resolved Life saving appliances and other equipment of cargo ships 500 GT shall have an annual survey. Vsl had survey 20NOV12 but several issues were not addressed. Both port and starboard lifeboats design flaws obstructing seating arrangements which reduced seating capacity from 28 to 24. See FormAB from Act# 4542980. SOLAS I/8; 40abc Mar 12, 13 Yes
Resolved Date Resolution Jun 12, 13 Conducted a PSC administrative document check. Received Cargo Ship Safety Equipment Certificate issued by NKK, and updated all applicable vessel information.
4545404
San Francisco, California
Mar 07, 13
Boarding - Agency Action Complete
4213793
Victoria, Texas
Jan 03, 12
Vessel Inspection - Approved Inspection
3991823
New Orleans, Louisiana
Apr 25, 11
Vessel Inspection - Approved Inspection
3913924
Lake Charles, Louisiana
Dec 24, 10
Vessel Inspection - Approved Inspection
3679346
San Francisco, California
Feb 12, 10
Vessel Inspection - Approved Inspection
3386497
New Orleans, Louisiana
Dec 30, 08
Vessel Operational Control - Agency Action Complete
3374548
San Francisco, California
Dec 06, 08
Vessel Inspection - Approved Inspection
4
0
System Subsystem Cause Documentation Logs/Records
Description Due Date Resolved 0199: Ballast water Management Plan requires training for all crew members with responsibilities regarding ballast operations and that training be recorded and validated: raining log is not current nor validated. Plan also requires a Record of Sediment be kept with the handling log and no records have been kept. Jan 05, 09 Yes
Resolved Date Resolution Dec 16, 08 Deficiency cleared based on receipt of NKK Cllass report #08VC0069, dated 12 DEC 08, that records were updated.
System Subsystem Cause Accommodation/Occupational Safety Refrigeration (air conditioning)
Description Due Date Resolved 0320: Air Conditioning room's intake ducting leading to main accommodation space supply ventilator is holed and wasted. In the event of a fire, oxygen cannot be secured to the area and could allow the fire to spread. Jan 05, 09 Yes
Resolved Date Resolution Dec 16, 08 Deficiency cleared based on receipt of NKK Cllass report #08VC0069, dated 12 DEC 08, that approved temporary repair was made with permanent repairs due by 25 MAR 09.
System Subsystem Cause Lifesaving Immersion Suits
Description Due Date Resolved 0663: During Abandon Ship Drill, observed several immersion suits too large for crew members. Additionally, lifesaving equipment certificate form E does not indicate that suits meet requirements of needing a life jacket; immersion suits have buoyant collar, a light, and a whistle. Jan 05, 09 Yes
Resolved Date Resolution Dec 16, 08 Deficiency cleared based on receipt of NKK Cllass report #08VC0069, dated 12 DEC 08, that suits were of suitable size, height range for universal suit is 1.40 meters to 1.90 meters. Personnel height was 1.57 meters to 1.77 meters.
System Subsystem Cause Construction/Loadline Markings
Description Due Date Resolved 1220: Load line is not of a contrasting color to the hull as per ICLL requirement. Load line was surveyed November 2, 2008. Appearance of the load lines on Port and Starboard side indicate that it has not been of a contrasting color since March dry-dock. Jan 05, 09 Yes
Resolved Date Resolution Dec 16, 08 Deficiency cleared based on receipt of NKK Cllass report #08VC0069, dated 12 DEC 08, that contrasting markings were in place.
3196822
New Orleans, Louisiana
May 02, 08
Vessel Operational Control - Agency Action Complete
3197073
WASHINGTON, District of Columbia
May 01, 08
Incident Investigation - Agency Action Complete
3147071
TEXAS CITY, Texas
Feb 13, 08
Vessel Inspection - Approved Inspection
3119548
Warrenton, Oregon
Jan 05, 08
Vessel Inspection - Agency Action Complete
2853132
CORPUS CHRISTI, Texas
Jan 09, 07
Vessel Inspection - Approved Inspection
2852265
CORPUS CHRISTI, Texas
Jan 08, 07
Vessel Inspection - Administrative Action
2850285
CORPUS CHRISTI, Texas
Jan 07, 07
Boarding - Agency Action Complete
2812294
Baltimore, Maryland
Nov 01, 06
Vessel Operational Control - Approved Inspection
2812864
Baltimore, Maryland
Nov 01, 06
Vessel Inspection - Approved Inspection
2813572
WASHINGTON, District of Columbia
Nov 01, 06
Incident Investigation - Agency Action Complete
2810476
STATEN ISLAND, New York
Oct 30, 06
Vessel Inspection - Approved Inspection
1
0
System Subsystem Cause Communications Alarms/Indicators Unknown
Description Due Date Resolved WHEN FIRE DETECTOR ON SHIP IS ACTIVATED, THERE IS NO AUDIBLE OR VISUAL ALARM IN ENGINE CONTROL ROOM TO ALERT RESPONSIBLE ENGINEER AS REQUIRED BY SOLAS II-2 7.4.2. INSTALL AUDIBLE AND VISUAL FIRE ALARM SO RESPONSIBLE ENGINEER CAN BE ALERTED OF ANY FIRE DETECTOR ACTIVATION TO THE SATISFACTION OF FLAG STATE BY NOVEMBER 30, 2006. Nov 30, 06 Yes
Resolved Date Resolution Nov 01, 06 Cleared deficiency
Documents
Issued
Expires
Agency
Certificate of Fitness - Chemical Carrier
January 20,2011
December 25,2015
N/A
Classification Document
August 15,2017
November 15,2018
DNV GL
International Certificate of Fitness - Chemical
August 15,2017
January 15,2018
DNV GL
International Load Line Certificate
January 19,2018
December 25,2020
DNV GL
International Oil Pollution Prevention Certificate
February 24,2016
December 25,2020
NKK
ISM - Document Of Compliance
June 28,2017
September 18,2021
ABS
ISM - Safety Management Certificate
September 29,2011
May 4,2016
ABS
Minimum Safe Manning Document
February 10,2016
MH
SOLAS Cargo Ship Safety Construction Certificate
January 19,2018
December 25,2020
DNV GL
SOLAS Cargo Ship Safety Equipment Certificate
April 16,2008
November 15,2009
NKK
SOLAS Cargo Ship Safety Radio Certificate
November 16,2007
November 15,2008
N/A
Tonnage Certificate, International
November 8,2017
December 25,2020
DNV GL