B. No. 230
Print Q88   
IMO/VIN Callsign Flag Service Year
991746 WCY3716 UNITED STATES Tank Barge 1993
Activity# Port Date Activity - Description Deficiencies
7150833 STATEN ISLAND, New York Mar 05, 21 Vessel Inspection - Agency Action Complete
7138166 STATEN ISLAND, New York Feb 09, 21 Vessel Inspection - Agency Action Complete
  1
SystemSubsystemCause
02 - Structural ConditionsN/A - No SubsystemDamaged By Earlier Event
DescriptionDue DateResolved
No extensive repairs to the hull or machinery which affect the safety of a vessel shall be made without the knowledge of the Officer in Charge, Marine Inspection. It was discovered that the barge had an allision with the tug EVENING BREEZE and may have sustained damage to the starboard quarter of the aft rake. Vessel must be made available for internal inspection of the area prior to movement.No
7105096 STATEN ISLAND, New York Dec 02, 20 Vessel Inspection - Approved Inspection
7026666 STATEN ISLAND, New York Aug 07, 20 Vessel Inspection - Agency Action Complete
7020497 STATEN ISLAND, New York Jul 31, 20 Vessel Inspection - Agency Action Complete
6727386 New Orleans, Louisiana Jul 03, 19 Vessel Inspection - Approved Inspection
6675433 CORPUS CHRISTI, Texas May 01, 19 Vessel Inspection - Approved Inspection
6647451 New Orleans, Louisiana Mar 22, 19 Vessel Inspection - Approved Inspection
6641796 CORPUS CHRISTI, Texas Mar 12, 19 Vessel Inspection - Approved Inspection
6484151 New Orleans, Louisiana Jul 16, 18 Vessel Inspection - Approved Inspection
6451893 New Orleans, Louisiana Jun 28, 18 Vessel Inspection - Approved Inspection
6316649 CORPUS CHRISTI, Texas Dec 01, 17 Vessel Inspection - Approved Inspection
  1
SystemSubsystemCause
ElectricalLighting (service)Improper/Lack of Maintenance
DescriptionDue DateResolved
Found boiler alarm (light) mount broken and hanging from conduit. Repair light to original configuration.Dec 15, 17Yes
Resolved DateResolution
Dec 08, 17Vessel rep provided picture of repaired light mount.
6105538 ST PETERSBURG, Florida Mar 21, 17 Vessel Inspection - Approved Inspection
6105538 Tampa, Florida Mar 21, 17 Vessel Inspection - Approved Inspection
5899378 New Orleans, Louisiana Jun 08, 16 Vessel Inspection - Approved Inspection
  1
SystemSubsystemCause
CommunicationsRadio CommunicationsInvalid
DescriptionDue DateResolved
Vsl has an expired EPIRB hydrostatic release unit (expiry date March 2016). EPRIB antenna is dry rooted through rubber coating exposing transmission wires. Provide proof of valid hydrostatic release unit and correction of EPIRB antenna wire degradation.Jun 15, 16Yes
Resolved DateResolution
Jun 15, 16Received email with picture of new antenna and hydrostatic release installed on the vessel.
5066100 New Orleans, Louisiana Feb 18, 15 Vessel Inspection - Approved Inspection
  4
SystemSubsystemCause
Deck/CargoBallast
DescriptionDue DateResolved
Crop and renew ballast piping where there is a visible leak in weld of previous doubler patch in #6 port ballast tank.Apr 18, 15Yes
Resolved DateResolution
Apr 02, 15Cropped and renewed piping and air tested for attending marine inspector
SystemSubsystemCause
Deck/CargoInert Gas System
DescriptionDue DateResolved
Crop and renew piping with constant stream leak on the IG scrubber overboard discharge line in #6 port ballast tank.Apr 18, 15Yes
Resolved DateResolution
Apr 02, 15Cropped and renewed piping and air tested for attending marine inspector
SystemSubsystemCause
ElectricalElectric Generation Source (service)
DescriptionDue DateResolved
Demonstrate overspeed shut down of #3 generator in presence of USCG Marine Inspector.Mar 18, 15Yes
Resolved DateResolution
Feb 18, 15Corrected on site.
SystemSubsystemCause
Deck/CargoCargo Transfer/Lightering (liquid)
DescriptionDue DateResolved
Demonstrate proper operation of emergency remote manual shut down of #1 engine prior to using #1 engine for cargo operations.Yes
Resolved DateResolution
Apr 02, 15Vessel showed attending marine inspector proper operation and shutdown of the #1 engine
4900288 CORPUS CHRISTI, Texas Jun 26, 14 Vessel Inspection - Approved Inspection
4890607 CORPUS CHRISTI, Texas Jun 16, 14 Vessel Inspection - Approved Inspection
  4
SystemSubsystemCause
ElectricalElectric Generation Source (service)
DescriptionDue DateResolved
Each generator prime mover must have an overspeed device independent of governor, as well as shutdown automatically upon loss of lubricating pressure. Prove proper operation of both to the satisfaction of the attending Coast Guard Inspector.Jul 20, 14Yes
Resolved DateResolution
Jun 20, 14
SystemSubsystemCause
ElectricalElectric Generation Source (service)
DescriptionDue DateResolved
Ground detection system on switchboard shows a ground on #2 & #3 generator. Prove proper operation of system.Jul 20, 14Yes
Resolved DateResolution
Jun 20, 14
SystemSubsystemCause
LifesavingInflatable Liferafts
DescriptionDue DateResolved
Hydrostatic release is expired on liferaft. Replace hydrostatic release.Jul 20, 14Yes
Resolved DateResolution
Jul 11, 14
SystemSubsystemCause
LifesavingLifebuoys
DescriptionDue DateResolved
Retro-reflective tape required on ring buoy. Correctly place tape on buoy to satisfaction of attending Coast Guard Inspector.Jul 20, 14Yes
Resolved DateResolution
Jul 07, 14Replaced retro on ring buoy.
4622674 Mobile, Alabama Jun 17, 13 Vessel Inspection - Approved Inspection
4618189 Mobile, Alabama Jun 12, 13 Vessel Inspection - Approved Inspection
  3
SystemSubsystemCause
Fire FightingSemiportable CO2 Fire ExtinguishersImproper/Lack of Maintenance
DescriptionDue DateResolved
LABEL B-V FIRE EXTINGUISHING STATIONS AS NECESSARY. PER 46CFR35.40-10Jun 26, 13Yes
Resolved DateResolution
Jun 18, 13Received photographic evidence of correction of deficiency.
SystemSubsystemCause
ElectricalElectrical Distribution System (service)Improper/Lack of Maintenance
DescriptionDue DateResolved
PROPERLY MOUNT JUNCTION BOX BELOW CARGO LINES FWD OF #65 CARGO TANK HATCH AND ALSO PROVIDE SCREW FOR COVER PLATE. PER 46CFR111.81-1Jun 26, 13Yes
Resolved DateResolution
Jun 17, 13Received photographic evidence that J-box was satisfactorily repaired.
SystemSubsystemCause
ElectricalElectrical Distribution System (service)Improper/Lack of Maintenance
DescriptionDue DateResolved
RENEW CONDUITS AS NEEDED FOR THE ELECTRICAL WIRES FEEDING TANK GAUGING SYSTEM. PER 46CFR111.60-5Jul 12, 13Yes
Resolved DateResolution
Jun 17, 13Received photographic evidence that J-box was satisfactorily repaired.
4436987 New Orleans, Louisiana Sep 13, 12 Vessel Inspection - Approved Inspection
4320404 New Orleans, Louisiana May 25, 12 Vessel Inspection - Approved Inspection
4288145 Morgan City, Louisiana Apr 16, 12 Vessel Inspection - Approved Inspection
4160551 ST PETERSBURG, Florida Oct 04, 11 Vessel Inspection - Agency Action Complete
4160551 Tampa, Florida Oct 04, 11 Vessel Inspection - Agency Action Complete
4144185 Morgan City, Louisiana Sep 12, 11 Vessel Inspection - Approved Inspection
  3
SystemSubsystemCause
Pollution Prevention/ResponsePrevention EquipmentImproper Installation
DescriptionDue DateResolved
Ensure that the cargo overfill alarm is visible over the entire cargo deck Also ensure the overfill alarm does interfere with the nav/ cargo lights.Sep 19, 12Yes
Resolved DateResolution
Sep 13, 12Cargo overfill alarms mast was elevated 6" over prior location and is visible to entire tank deck.
SystemSubsystemCause
Deck/CargoCargo Transfer/Lightering (liquid)Improper/Lack of Maintenance
DescriptionDue DateResolved
Repair or replace valve indicators for all tanks.Sep 19, 12Yes
Resolved DateResolution
Sep 13, 12All cargo tank valves were observed with indicators.
SystemSubsystemCause
Deck/CargoCargo Transfer/Lightering (liquid)Improper/Lack of Maintenance
DescriptionDue DateResolved
Replace or Repair cargo sight glasses on all tanks. The vessel is restricted from carrying cargos that require closed gauging until the cargo sight glasses have been repaired or replaced.Yes
Resolved DateResolution
May 25, 12Attended vsl and witnessed the presence of MMC enhanced closed gauging system.
4104245 STATEN ISLAND, New York Aug 03, 11 Vessel Inspection - Agency Action Complete
4133033 ST PETERSBURG, Florida Jun 13, 11 Vessel Inspection - Approved Inspection
  4
SystemSubsystemCause
LifesavingLifejacket/PFD (General)
DescriptionDue DateResolved
Vessel is restricted to carrying three (3) crewmembers until providing proper lifejacket to comply with requirements found in 46 CFR 199.620.Jun 30, 11Yes
Resolved DateResolution
Jun 16, 11
SystemSubsystemCause
Pollution Prevention/ResponsePrevention Equipment
DescriptionDue DateResolved
Vessel Master may not conduct cargo operations until satisfactory test of audible alarm for overfill device. Alarm must comply with visual and audible requirements found in 46 CFR 39.20-9(a).Jun 30, 11Yes
Resolved DateResolution
Jun 16, 11
SystemSubsystemCause
Deck/CargoInert Gas System
DescriptionDue DateResolved
Vessel master must prove proper operation and conduct satisfactory test procedures for the Inert Gas System I.A.W. 46 CFR 32.53-5. Vessel may not conduct cargo operations until satisfactory test is witnessed by USCG Marine Inspector.Jun 30, 11Yes
Resolved DateResolution
Jun 16, 11
SystemSubsystemCause
Deck/CargoVapor Control Systems
DescriptionDue DateResolved
Vessel's vapor control piping must be properly painted to comply with requirements found in 46 CFR 39.20-1(d).Jun 30, 11Yes
Resolved DateResolution
Jun 16, 11
4133033 Tampa, Florida Jun 13, 11 Vessel Inspection - Approved Inspection
  4
SystemSubsystemCause
LifesavingLifejacket/PFD (General)
DescriptionDue DateResolved
Vessel is restricted to carrying three (3) crewmembers until providing proper lifejacket to comply with requirements found in 46 CFR 199.620.Jun 30, 11Yes
Resolved DateResolution
Jun 16, 11
SystemSubsystemCause
Pollution Prevention/ResponsePrevention Equipment
DescriptionDue DateResolved
Vessel Master may not conduct cargo operations until satisfactory test of audible alarm for overfill device. Alarm must comply with visual and audible requirements found in 46 CFR 39.20-9(a).Jun 30, 11Yes
Resolved DateResolution
Jun 16, 11
SystemSubsystemCause
Deck/CargoInert Gas System
DescriptionDue DateResolved
Vessel master must prove proper operation and conduct satisfactory test procedures for the Inert Gas System I.A.W. 46 CFR 32.53-5. Vessel may not conduct cargo operations until satisfactory test is witnessed by USCG Marine Inspector.Jun 30, 11Yes
Resolved DateResolution
Jun 16, 11
SystemSubsystemCause
Deck/CargoVapor Control Systems
DescriptionDue DateResolved
Vessel's vapor control piping must be properly painted to comply with requirements found in 46 CFR 39.20-1(d).Jun 30, 11Yes
Resolved DateResolution
Jun 16, 11
4030362 WASHINGTON, District of Columbia May 31, 11 Incident Investigation - Agency Action Complete
3956008 WASHINGTON, District of Columbia Feb 26, 11 Incident Investigation - Agency Action Complete
3757590 STATEN ISLAND, New York Jun 04, 10 Vessel Inspection - Agency Action Complete
3681120 STATEN ISLAND, New York Feb 17, 10 Vessel Inspection - Agency Action Complete
  2
SystemSubsystemCause
LifesavingImmersion SuitsUnknown
DescriptionDue DateResolved
Make proper repairs to inflatable cushion hose on immersion suit.Mar 17, 10Yes
Resolved DateResolution
Mar 17, 10Rcv''''d copy of invoice for replacement immersion suit.
SystemSubsystemCause
ElectricalLighting (emergency)Unknown
DescriptionDue DateResolved
Prove proper operation of emergency lighting fixture in generator space.Mar 17, 10Yes
Resolved DateResolution
Mar 17, 10Rcv''''d copy of invoice from vsl rep for lighting repair.
3654078 STATEN ISLAND, New York Dec 22, 09 Vessel Inspection - Agency Action Complete
3577395 WASHINGTON, District of Columbia Aug 26, 09 Incident Investigation - Agency Action Complete
3492955 STATEN ISLAND, New York Jun 02, 09 Vessel Inspection - Agency Action Complete
3474696 Baltimore, Maryland May 14, 09 Enforcement - Agency Action Complete
3456542 WASHINGTON, District of Columbia Apr 17, 09 Incident Investigation - Agency Action Complete
3193975 ST PETERSBURG, Florida Apr 28, 08 Vessel Inspection - Approved Inspection
3193975 Tampa, Florida Apr 28, 08 Vessel Inspection - Approved Inspection
3163087 CORPUS CHRISTI, Texas Mar 12, 08 Vessel Inspection - Agency Action Complete
  1
SystemSubsystemCause
Construction/LoadlineHullDamaged By Earlier Event
DescriptionDue DateResolved
14" fracture located approx 6' above the water line on the Stbd side, in way of the transition between the tug notch and the stern plaiting.Mar 19, 08Yes
Resolved DateResolution
Mar 13, 08Fracture was gouged and back-gouged, then welded. A dye penetrate test was conducted.
3161620 CORPUS CHRISTI, Texas Mar 11, 08 Vessel Inspection - Approved Inspection
3091744 PHILADELPHIA, Pennsylvania Nov 02, 07 Vessel Transfer Monitor - Agency Action Complete
2992892 WASHINGTON, District of Columbia Jul 12, 07 Incident Investigation - Agency Action Complete
2960686 STATEN ISLAND, New York Jun 13, 07 Vessel Inspection - Approved Inspection
  1
SystemSubsystemCause
Deck/CargoHolds/TanksImproper Installation
DescriptionDue DateResolved
Prove operation of liquid overfill protection systemJun 21, 07Yes
Resolved DateResolution
Jun 18, 07Recieved Seviceman''s Report stating that overfill alarm on all tanks have been tested and found satisfactory
2781875 STATEN ISLAND, New York Sep 19, 06 Enforcement - Agency Action Complete
2775185 WASHINGTON, District of Columbia Sep 11, 06 Incident Investigation - Agency Action Complete
2756265 STATEN ISLAND, New York Aug 22, 06 Vessel Transfer Monitor - Approved Inspection
2743865 Washington, District of Columbia Aug 11, 06 Vessel Inspection - Security Plan Approved by MSC
2692763 STATEN ISLAND, New York Jun 27, 06 Vessel Inspection - Approved Inspection
  2
SystemSubsystemCause
Deck/CargoCargo Heating
DescriptionDue DateResolved
Do to maintenance vessel is not to carry cargoes requiring use of the Thermal Fluid Heater until proper operation of the unit has bee demonstrated to the attending USCG Marine Inspector.Yes
Resolved DateResolution
Aug 08, 06Completed maintenance and preformed proper tests to the satisfaction of the attending marine inspector.
SystemSubsystemCause
Accommodation/Occupational SafetyOccupational Safety
DescriptionDue DateResolved
Provide an Oxygen Meter for vessel crew to check O2 Levels on the IGS System.Aug 21, 06Yes
Resolved DateResolution
Aug 08, 06Vessel purchased new meter.
2645682 STATEN ISLAND, New York May 10, 06 Vessel Inspection - Agency Action Complete
2603051 Washington, District of Columbia Mar 15, 06 Vessel Inspection - Security Plan Approved by MSC
2578886 Washington, District of Columbia Feb 03, 06 Vessel Inspection - Administrative Action
2400501 STATEN ISLAND, New York Jun 23, 05 Vessel Inspection - Agency Action Complete
2356896 NEW HAVEN, Connecticut May 13, 05 Vessel Transfer Monitor - Agency Action Complete
2309851 Washington, District of Columbia Mar 14, 05 Vessel Inspection - Security Plan Approved by MSC
2090773 STATEN ISLAND, New York Jun 07, 04 Vessel Inspection - Agency Action Complete
  5
SystemSubsystemCause
Deck/CargoMooring/AnchoringPlaced in Improper Service
DescriptionDue DateResolved
Inspect and or repair fwd/aft fender winch brake as needed to satisfaction of attending marine inspector, prior to use.Yes
Resolved DateResolution
Aug 20, 04
SystemSubsystemCause
Deck/CargoMooring/Anchoring
DescriptionDue DateResolved
Procure handle pin prior to operating aft fender winch to satisfaction of attending marine inspector.Yes
Resolved DateResolution
Aug 20, 04
SystemSubsystemCause
DocumentationManuals/Policy Documentation
DescriptionDue DateResolved
Procure operating procedures of fender winch. Provide copy to USCG marine inspector prior to use of said winch.Yes
Resolved DateResolution
Jun 16, 04
SystemSubsystemCause
EngineeringPressure VesselDamaged By Earlier Event
DescriptionDue DateResolved
Replace cracked flame sight glass on thermal fluid heater.Jul 16, 04Yes
Resolved DateResolution
Aug 20, 04
SystemSubsystemCause
EngineeringPressure VesselUnknown
DescriptionDue DateResolved
Replace oil pressure gauge on thermal fluid heater. Gauge is inoperable.Jul 16, 04Yes
Resolved DateResolution
Aug 20, 04
2090775 WASHINGTON, District of Columbia Jun 07, 04 Incident Investigation - Agency Action Complete
2080667 Washington, District of Columbia May 28, 04 Vessel Inspection - Security Plan Approved by MSC
1962415 Washington, District of Columbia Dec 09, 03 Vessel Inspection - ASP Criteria Met
1777781 ST PETERSBURG, Florida Apr 21, 03 Vessel Inspection - Approved Inspection
1777781 Tampa, Florida Apr 21, 03 Vessel Inspection - Approved Inspection
1764517 STATEN ISLAND, New York Mar 28, 03 Vessel Inspection - Administrative Action
1762553 STATEN ISLAND, New York Mar 25, 03 Vessel Inspection - Approved Inspection
  5
SystemSubsystemCause
Deck/CargoInert Gas System
DescriptionDue DateResolved
IGS system not permitted to be used until proper operation (incl tests, shutdowns, etc) is proven to the satisfaction of CG inspectorsYes
Resolved DateResolution
Jun 12, 03
SystemSubsystemCause
EngineeringCompressed Air System (start air)
DescriptionDue DateResolved
Make air receiver ready for internal exam (overdue since 2002) *Due 31 Mar 03 or next Drydock LEGACY COMPONENT DESC: Receiver/BottleYes
Resolved DateResolution
Jun 12, 03
SystemSubsystemCause
ElectricalElectric Generation Source (service)
DescriptionDue DateResolved
Make generators #1, #2, & #3 ready for inspection.Yes
Resolved DateResolution
Jun 12, 03
SystemSubsystemCause
Deck/CargoCargo Heating
DescriptionDue DateResolved
Make thermal fluid heater ready for testing LEGACY COMPONENT DESC: Thermal Fluid HeaterYes
Resolved DateResolution
Mar 25, 03
SystemSubsystemCause
Deck/CargoCargo Transfer/Lightering (liquid)
DescriptionDue DateResolved
No commercial operations permitted until proper operation of high level alarms is proven to the satisfaction of CG inspectors.Yes
Resolved DateResolution
Jun 12, 03
1639713 GRETNA, Louisiana Jul 01, 02 Vessel Inspection - Approved Inspection
  5
SystemSubsystemCause
Construction/Loadline
DescriptionDue DateResolved
ABS issued requirement to re-position loadline in correct location.Aug 02, 02Yes
Resolved DateResolution
Jun 12, 03
SystemSubsystemCause
ElectricalElectric Generation Source (service)Unknown
DescriptionDue DateResolved
Repair compressor on #3 generator.Aug 02, 02Yes
Resolved DateResolution
Jun 12, 03
SystemSubsystemCause
Deck/CargoInert Gas System
DescriptionDue DateResolved
Repair high water level indicator for flue gas scrubber on Inert Gas System, prior to loading cargoes requiring system.Aug 02, 02Yes
Resolved DateResolution
Jun 12, 03
SystemSubsystemCause
Deck/CargoCargo Transfer/Lightering (liquid)Unknown
DescriptionDue DateResolved
Repair sight glass to #1 cargo tank, stbd side.Aug 02, 02Yes
Resolved DateResolution
Jun 12, 03
SystemSubsystemCause
EngineeringPressure VesselUnknown
DescriptionDue DateResolved
Replace relief valve on hot water heater. LEGACY COMPONENT DESC: Relief ValveAug 02, 02Yes
Resolved DateResolution
Jun 12, 03
1626092 New Orleans, Louisiana Jun 04, 02 Vessel Inspection - Approved Inspection
  4
SystemSubsystemCause
LifesavingLifebuoys
DescriptionDue DateResolved
Prior to sailing replace line on ring bouys with required dark color and length IAW 46CFR199.70(a)(3)(A) and (E).Jul 04, 02Yes
Resolved DateResolution
Jun 04, 02
SystemSubsystemCause
Deck/CargoInert Gas System
DescriptionDue DateResolved
Provide zero calibration gas for IGS, prior to conducting cargo operations that require the IGS.Jul 04, 02Yes
Resolved DateResolution
Jun 04, 02
SystemSubsystemCause
Deck/CargoCargo Transfer/Lightering (liquid)
DescriptionDue DateResolved
Repair pressure vacuum valves to operating condition prior to loading any cargoes to #1 stbd, #3 stbd and #3 port cargo tanks.Jul 04, 02Yes
Resolved DateResolution
Jun 04, 02
SystemSubsystemCause
Deck/CargoBallast
DescriptionDue DateResolved
Repair valve to #5 stbd ballast tank.Jul 04, 02Yes
Resolved DateResolution
Jun 04, 02
1436571 New Orleans, Louisiana May 18, 01 Vessel Inspection - Agency Action Complete
1062452 New Orleans, Louisiana Mar 28, 01 Vessel Inspection - Administrative Action
1466778 Miami Beach, Florida Mar 26, 01 Vessel Inspection - Agency Action Complete
1061382 New Orleans, Louisiana Mar 12, 01 Vessel Inspection - Agency Action Complete
1060101 New Orleans, Louisiana Mar 07, 01 Vessel Inspection - Agency Action Complete
1060435 New Orleans, Louisiana Mar 06, 01 Vessel Inspection - Agency Action Complete
283668 New Orleans, Louisiana Oct 30, 00 Vessel Inspection - Agency Action Complete
1389097 New Orleans, Louisiana May 24, 00 Vessel Inspection - Agency Action Complete
  4
SystemSubsystemCause
Deck/CargoUnknown
DescriptionDue DateResolved
PRIOR TO LOADING CARGO, REPAIR OVERFILL AND HIGH LEVEL ALARMS. Jun 24, 00Yes
Resolved DateResolution
May 25, 00
SystemSubsystemCause
Deck/CargoUnknown
DescriptionDue DateResolved
REPAIR POSITION INDICATORS ON CARGO VALVES FOR #8 PORT AND #7 STBD CARGO TANKS. Jun 24, 00Yes
Resolved DateResolution
May 25, 00
SystemSubsystemCause
Deck/CargoUnknown
DescriptionDue DateResolved
REPLACE FLEXIBLE FUEL OIL LINE ON THERMAL FLUID HEATER PRIOR TO OPERATION. Jun 24, 00Yes
Resolved DateResolution
May 25, 00
SystemSubsystemCause
LifesavingUnknown
DescriptionDue DateResolved
REPLACE LIGHTS ON LIFE JACKETS WITH APPROVED LIGHTS PRIOR TO SAILING. Jun 24, 00Yes
Resolved DateResolution
May 24, 00
493803 Warrenton, Oregon Aug 31, 99 Vessel Transfer Monitor - Agency Action Complete
1386468 Seattle, Washington Mar 31, 99 Vessel Inspection - Agency Action Complete
  8
SystemSubsystemCause
ElectricalUnknown
DescriptionDue DateResolved
INSTALL PROPER ELECTRICAL CONNECTORS FOR ALL BATTERY CONNECTIONS. Apr 02, 99Yes
Resolved DateResolution
Apr 02, 99
SystemSubsystemCause
LifesavingUnknown
DescriptionDue DateResolved
PROVIDE ADEQUATE EMERGENCY OUTFIT, AND PROVIDE CREW TRAINING FOR DONNING AND USE OF OUTFIT. Apr 08, 99Yes
Resolved DateResolution
Apr 08, 99
SystemSubsystemCause
LifesavingUnknown
DescriptionDue DateResolved
PROVIDE CALIBRATION TEST KIT FOR EXPLOSIMETER. Apr 08, 99Yes
Resolved DateResolution
Apr 08, 99
SystemSubsystemCause
EngineeringUnknown
DescriptionDue DateResolved
PROVIDE MARINE GRADE F/O FILTERS FOR IGS AND SSG'S. (MISSING FLAME IMPENGMENT BOWLS) Apr 08, 99Yes
Resolved DateResolution
Apr 08, 99
SystemSubsystemCause
Fire FightingUnknown
DescriptionDue DateResolved
PROVIDE VAPOR TIGHT SEALS FOR CARGO PUMP SHAFTING BULKHEAD PENETRATIONS. Apr 08, 99Yes
Resolved DateResolution
Apr 08, 99
SystemSubsystemCause
Fire FightingUnknown
DescriptionDue DateResolved
REMOVE ALL EXCESSIVE PAINT, FLAMMABLE & COMBUSTIBLE LIQUIDS FROM BARGE. PROVIDE ADEQUATE STROAGE LOCKER FOR REMAINING FLAMMABLE & COMBUSTIBLE LIQUIDS. Apr 08, 99Yes
Resolved DateResolution
Apr 08, 99
SystemSubsystemCause
Fire FightingUnknown
DescriptionDue DateResolved
REPAIR AND PROVE PROPER OPERATION OF OXYGEN METERS. Apr 08, 99Yes
Resolved DateResolution
Apr 08, 99
SystemSubsystemCause
EngineeringUnknown
DescriptionDue DateResolved
REPAIR LEAK IN STBD AMIDSHIPS F/O TANK DRAIN VALVE. Apr 08, 99Yes
Resolved DateResolution
Apr 08, 99
109462 WASHINGTON, District of Columbia Mar 28, 99 Incident Investigation - Agency Action Complete
486327 ST PETERSBURG, Florida Oct 11, 98 Vessel Transfer Monitor - Agency Action Complete
486327 Tampa, Florida Oct 11, 98 Vessel Transfer Monitor - Agency Action Complete
1394981 New Orleans, Louisiana Jun 26, 98 Vessel Inspection - Agency Action Complete
1123755 San Pedro, California Apr 24, 98 Vessel Inspection - Agency Action Complete
  1
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
CONDUCT DRYDOCK INSPECTION OF THE VESSEL NOT LATER THAN 31MAY98. Apr 24, 98Yes
Resolved DateResolution
Apr 24, 98
1456596 ST PETERSBURG, Florida Mar 31, 98 Vessel Inspection - Agency Action Complete
  11
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Clean cargo tank adjacent to #5P ballast tank and conduct a leak test I.W.O. the last bay where there is evidence of a cargo leak. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and insert to the attending class surveyor or Marine Inspectors satisfaction I.W.O. frames #1 & 2 at side longs 4 & 6 in #3S wing void. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/inser the deep web frame #1 between sidelongs #4 & #6 in the#2 port wing ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/insert #7 swash bulkhead between sidelongs #12 & #15 in #3P ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/insert swash bulkhead #1 between sidelongs #13 & #15 in #3P ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/insert swash bulkhead #4 between sidelongs #4 & #6 in #3P ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/insert swash bulkhead #5 at bilge knuckle in #3P ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
DocumentationUnknown
DescriptionDue DateResolved
Provide replacement IOPP Certificate from LOSMS or a certified to be a truecopy of the issued IOPP Certificate, to replace the missing certificate. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
LifesavingUnknown
DescriptionDue DateResolved
Remove excessive quanity of spare oil containers from machinery spaces I.A.W. 46/147.45   Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Repair leaking ballast piping in #6P ballast tank, last bay. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Deck/CargoUnknown
DescriptionDue DateResolved
Test Inert Gas System in presence of a Marine Inspector. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
1456596 Tampa, Florida Mar 31, 98 Vessel Inspection - Agency Action Complete
  11
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Clean cargo tank adjacent to #5P ballast tank and conduct a leak test I.W.O. the last bay where there is evidence of a cargo leak. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and insert to the attending class surveyor or Marine Inspectors satisfaction I.W.O. frames #1 & 2 at side longs 4 & 6 in #3S wing void. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/inser the deep web frame #1 between sidelongs #4 & #6 in the#2 port wing ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/insert #7 swash bulkhead between sidelongs #12 & #15 in #3P ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/insert swash bulkhead #1 between sidelongs #13 & #15 in #3P ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/insert swash bulkhead #4 between sidelongs #4 & #6 in #3P ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Crop and renew/insert swash bulkhead #5 at bilge knuckle in #3P ballast tank. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
DocumentationUnknown
DescriptionDue DateResolved
Provide replacement IOPP Certificate from LOSMS or a certified to be a truecopy of the issued IOPP Certificate, to replace the missing certificate. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
LifesavingUnknown
DescriptionDue DateResolved
Remove excessive quanity of spare oil containers from machinery spaces I.A.W. 46/147.45   Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
Repair leaking ballast piping in #6P ballast tank, last bay. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
SystemSubsystemCause
Deck/CargoUnknown
DescriptionDue DateResolved
Test Inert Gas System in presence of a Marine Inspector. Mar 31, 98Yes
Resolved DateResolution
Mar 31, 98
61396 WASHINGTON, District of Columbia Mar 10, 98 Incident Investigation - Agency Action Complete
784383 Houston, Texas Dec 24, 97 Vessel Inspection - Agency Action Complete
  1
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
MAKE PERMANENT REPAIRS TO TWO HOLES LOCATED PORT BOW, APPROXIMATELY 2 FEET ABOVE THE WATERLINE. Dec 24, 97Yes
Resolved DateResolution
Dec 24, 97
781985 TEXAS CITY, Texas Dec 23, 97 Vessel Inspection - Agency Action Complete
  1
SystemSubsystemCause
Construction/LoadlineUnknown
DescriptionDue DateResolved
MAKE PERMENT REPAIRS TO THE DAMAGE IN THE PORT SIE OF THE BOW RAKE TO THE APPROVAL OF CG MARINE INSPECTOR PRIOR TO NEXT LOADING OPERATION. Dec 23, 97Yes
Resolved DateResolution
Dec 23, 97
106157 WASHINGTON, District of Columbia Dec 23, 97 Incident Investigation - Agency Action Complete
462341 ST PETERSBURG, Florida Dec 06, 97 Vessel Transfer Monitor - Agency Action Complete
462341 Tampa, Florida Dec 06, 97 Vessel Transfer Monitor - Agency Action Complete
532818 ST PETERSBURG, Florida Jul 31, 97 Vessel Transfer Monitor - Agency Action Complete
532818 Tampa, Florida Jul 31, 97 Vessel Transfer Monitor - Agency Action Complete
1105447 Seattle, Washington May 16, 97 Vessel Inspection - Agency Action Complete
1437230 San Pedro, California Apr 16, 97 Vessel Inspection - Agency Action Complete
  6
SystemSubsystemCause
LifesavingUnknown
DescriptionDue DateResolved
Provide a current hydrostatic release for the EPIRB. May 01, 97Yes
Resolved DateResolution
Apr 24, 97
SystemSubsystemCause
DocumentationUnknown
DescriptionDue DateResolved
Provide a letter of certification for vapor control system operation in accordance with 46CFR39.10-11. Apr 18, 97Yes
Resolved DateResolution
Apr 21, 97
SystemSubsystemCause
Deck/CargoUnknown
DescriptionDue DateResolved
Provide a record by a qualified 3rd party technician or demonstrate to an attending marine inspector the operational tests and checks on the thermal fluid heater(TFH) in accordance with 46CFR61.30-20 and test in accordance with vessel's approved test procedures dated 21Apr93 before operating TFH. Apr 24, 97Yes
Resolved DateResolution
Apr 28, 97
SystemSubsystemCause
Deck/CargoUnknown
DescriptionDue DateResolved
Provide a record from a qualified third party technician or demonstrate to an attending marine inspector all installed alarms and shutdowns on the inert gas system. Apr 16, 97Yes
Resolved DateResolution
Apr 16, 97
SystemSubsystemCause
Deck/CargoUnknown
DescriptionDue DateResolved
Provide a record from a qualified third party technician or demonstrate to an attending marine inspector that the condition of the thermal fluid heater is satisfactory in accordance with 46CFR61.30-15. This item must be corrected before the thermal fluid heater may be operated. Apr 24, 97Yes
Resolved DateResolution
Apr 28, 97
SystemSubsystemCause
ElectricalUnknown
DescriptionDue DateResolved
Repair electrical ground on B phase, port deckhouse lighting panel. Apr 16, 97Yes
Resolved DateResolution
Apr 16, 97
5468 WASHINGTON, District of Columbia May 01, 96 Incident Investigation - Agency Action Complete
1374588 San Pedro, California Apr 18, 96 Vessel Inspection - Agency Action Complete
879040 STATEN ISLAND, New York Dec 07, 95 Vessel Inspection - Agency Action Complete
1175683 San Pedro, California Apr 12, 95 Vessel Inspection - Agency Action Complete
  4
SystemSubsystemCause
DocumentationUnknown
DescriptionDue DateResolved
PROVIDE CURRENT STABILITY LETTER DATED 22 DECEMBER 1993 ON BOARD. Apr 12, 95Yes
Resolved DateResolution
Apr 12, 95
SystemSubsystemCause
DocumentationUnknown
DescriptionDue DateResolved
PROVIDE PROOF OF COMPLIANCE TO DRUG TESTING PROGRAM IN ACOORDANCE WITH  46 CFR PART 16. Apr 30, 95Yes
Resolved DateResolution
May 01, 95
SystemSubsystemCause
DocumentationUnknown
DescriptionDue DateResolved
PROVIDE PROOF THAT THE VESSEL DO NOT CARRY CARGOES WITH BENZENE CONTENTS OF0.5 PERCENT OR MORE. Apr 28, 95Yes
Resolved DateResolution
Apr 28, 95
SystemSubsystemCause
ElectricalUnknown
DescriptionDue DateResolved
REPAIR THE GENERAL ALARM ROTATING BEACON LIGHT IN THE GENERATOR ROOM AND THE PUMP ROOM. May 01, 95Yes
Resolved DateResolution
May 01, 95
1328432 San Pedro, California Jun 16, 94 Vessel Inspection - Agency Action Complete
1161801 New Orleans, Louisiana Jan 13, 94 Vessel Inspection - Agency Action Complete
1456103 New Orleans, Louisiana Apr 22, 93 Vessel Inspection - Agency Action Complete
Documents Issued Expires Agency
CERTIFICATE OF DOCUMENTATION February 13,2021 February 28,2022 USCG
Certificate of Inspection March 26,2001 March 26,2003 N/A
Certificate of Inspection - Amended March 25,2003 March 25,2008 N/A
Classification Document March 26,2012 March 25,2017 ABS
International Load Line Certificate March 26,2012 March 25,2017 N/A
International Oil Pollution Prevention Certificate May 18,2001 May 18,2006 N/A
ISM - Document Of Compliance September 13,2012 September 18,2017 ABS
ISM - Safety Management Certificate September 13,2012 September 12,2017 N/A
Load Line Certificate (Coastwise) July 1,2003 April 30,2008 ABS
Stability Letter March 8,2012 ABS
Tonnage Certificate, International April 14,1993 ABS